Lighting the spaces people pass through
Stairwells and corridors are used by everyone but occupied by no one for long. They need to be safe to walk at all hours, they are part of the building's exit route, and they often run lights 24 hours a day. That combination makes them one of the best places in a building to save energy with LED and sensors, as long as egress and emergency requirements are met. This guide covers fixture choices, light levels, controls and code points for stairwells, corridors and hallways in commercial, multifamily and institutional buildings.

Typical light levels
General planning ranges based on IES guidance:
- Corridors in offices, schools and healthcare: roughly 10–20 fc, more where tasks happen.
- Stairwells: roughly 10–20 fc on treads and landings while in use.
- Parking garage stairs and service corridors: similar levels, with attention to even light on the steps.
Building and fire codes set minimum illumination for exit paths, including stairs, and many codes require more light on stairs than on the rest of the egress path. Check the code your jurisdiction has adopted; we cannot tell you what applies to a specific building.
Stairwell lighting
Fixture types
- Wall-mounted stairwell fixtures at landings, often wraparound or linear shapes, light both the landing and the flights above and below.
- Ceiling-mounted linear or strip fixtures on landings and over flights.
- Vapor tight fixtures in exterior stairs, garage stairs and service stairs exposed to weather or washdown. See the vapor tight lighting guide.
Browse stairwell lighting fixtures.
Placement tips
- Light every landing and every flight; dark treads cause falls.
- Mount fixtures where they can be reached safely for service, not over the open stairwell where a ladder cannot stand.
- Avoid fixtures that throw glare into the eyes of people walking down the stairs.
- Light the nosing (edge) of each step evenly so depth is easy to judge.
Corridor lighting
- Drop-ceiling corridors: 2x2 or 1x4 panels or troffers in a single row. See the troffer and flat panel buying guide.
- Hard ceilings and service corridors: surface-mount linear or strip fixtures in a continuous or spaced row.
- Long corridors: space fixtures evenly so there are no dark gaps between pools of light, and light the walls as well as the floor.
- Back-of-house corridors: durable strip or vapor tight fixtures that hold up to carts and pallet jacks.
Bi-level and sensor control
Stairwells and corridors are often empty. Bi-level control keeps lights at a low standby level when no one is present and raises them to full when a sensor detects someone. LEDs are well suited to this because they change level instantly and are not harmed by frequent switching.
- Energy codes based on ASHRAE 90.1 and the IECC commonly require automatic reduction of stairwell and some corridor lighting when unoccupied. Requirements vary by code edition and jurisdiction, so check what applies.
- Choose a standby level that still meets egress requirements in your jurisdiction.
- Set sensor timeouts long enough that lights do not drop while someone is still on the stairs.
- In stairwells, place sensors so they see people coming from both directions and from each door.
Some fixtures offer a built-in sensor or a sensor base option, such as the 4 ft strip light with sensor base and 2x2 panel with sensor. Learn more in photocells and motion sensors and 0–10V dimming and controls, and browse motion activated LED lights.
Emergency and exit lighting
Stairwells and corridors are usually part of the required means of egress. That means:
- Emergency lighting must keep the path lit for a required period after power loss, commonly 90 minutes.
- Exit signs must mark the route and stair doors.
- Emergency fixtures must be tested on a regular schedule.
You can meet this with emergency drivers inside selected fixtures, separate emergency units, or a generator or central inverter system. See emergency lighting and exit sign basics and emergency battery backup lighting.
Durability and vandal resistance
Public stairwells, schools, transit and multifamily buildings see abuse. Consider:
- Impact-resistant lenses and housings. See IK ratings and shatterproof fixtures.
- Tamper-resistant screws where fixtures are within reach.
- Sealed fixtures in exterior or garage stairs. See IP ratings.
Color temperature
3500K–4000K is common in offices, schools, healthcare and multifamily corridors. 4000K–5000K suits service stairs, garages and industrial corridors. Keep CCT consistent with the spaces the corridor connects. See 3000K vs. 4000K vs. 5000K.
Upgrading old stairwell lighting
Many stairwells still run fluorescent wraparounds or compact fluorescent fixtures 24 hours a day. Switching to LED with bi-level sensors often produces some of the fastest paybacks in a building, because the old fixtures never turn off. See the fluorescent to LED guide and LED savings and payback.
Frequently asked questions
What is a bi-level stairwell light?
A fixture that runs at a low standby level when the stairwell is empty and switches to full brightness when its sensor detects someone.
Do stairwell lights have to stay on 24/7?
Egress paths must be lit while the building is occupied, but many energy codes allow, or require, lights to drop to a lower level when no one is present. Check your local code.
How bright should a corridor be?
Commonly about 10–20 fc, with even light along the length and on the walls.
Can stairwell fixtures include emergency backup?
Many can, with an emergency driver or a separate emergency unit. Check each product page for options.
Related guides
- Emergency lighting and exit sign basics
- Photocells and motion sensors
- Troffer and flat panel buying guide
- Parking garage lighting guide
- School lighting guide
- All lighting resources
Related products and guides
- stairwell lighting fixtures
- 2x2 LED troffer with sensor
- emergency battery backup lighting
- motion activated LED lights
- IP ratings and wet locations
Planning a project? Request a free lighting layout and we'll suggest fixtures and quantities.