Warehouse Lighting Guide

How to light a warehouse with LED

A good warehouse lighting plan puts enough light on the floor and on rack faces for people to pick, read labels and drive forklifts safely, without paying to light empty aisles all night. For most buildings that means LED high bays sized to the ceiling height, a layout that follows the racking, and occupancy sensors in low-traffic areas. This guide walks through each decision in the order you would make it on a real job.

Warehouse aisle with tall pallet racking and stocked shelves under overhead lighting

Step 1: Break the building into zones

Very few warehouses need one light level everywhere. Walk the building, or mark up a floor plan, and split it into zones. Each zone gets its own target and often its own fixture type:

  • Bulk and pallet storage: floor-stacked or deep racking that is visited a few times a day.
  • Active picking aisles: rack aisles where people read labels and pick cases or eaches all shift.
  • Open floor and staging: areas where pallets are built, wrapped and staged.
  • Packing, shipping and receiving: benches and doors where paperwork, scanning and inspection happen.
  • Loading docks: the inside of dock doors plus the truck court outside. See our loading dock and security lighting guide.
  • Special areas: coolers and freezers, battery charging, mezzanines, offices and break rooms.

Step 2: Set a light level for each zone

The ranges below are typical targets used across the industry, based on published IES recommendations. They are a starting point for planning, not a code requirement. Your client, insurer, or a local code may ask for something different.

Area Typical average target
Inactive or bulk storage About 5–10 foot-candles
Active storage, pallet racking About 10–20 fc
Picking aisles with label reading About 20–30 fc on the rack face
Open floor, staging, forklift traffic About 20–30 fc
Packing, shipping, receiving benches About 30–50 fc
Inspection or detailed work 50 fc and up, often with task lights

For a refresher on foot-candles and the lumen method, see how many lumens do I need?

Step 3: Match the fixture to the ceiling height

Mounting height drives both the fixture type and the wattage. As a rough guide for open areas:

These are planning ranges. The real answer depends on the target light level, the reflectance of the floor and racking, and the optics on the fixture you pick. Our high bay vs. low bay guide and the blog post on warehouse lighting by ceiling height go deeper.

Steel Tech Lights LED UFO high bay light with selectable wattage for warehouse open floors

Step 4: UFO or linear high bays?

Both work in warehouses. The difference is the shape of the light they put down.

UFO (round) high bays

Round fixtures throw a round pattern. They are quick to hang from a hook or pendant and are the usual pick for open floors, staging areas, and buildings without tall racking. Browse UFO high bays or the selectable 100–150W UFO.

Linear high bays

Linear fixtures throw a long, narrow pattern that follows an aisle. Hung in a row down the center of each rack aisle, they put light on the rack faces where people read labels, instead of on the top of the racks. Browse linear high bays, including the 6G and 7G series.

Steel Tech Lights 2 ft LED linear high bay light for warehouse rack aisles

Step 5: Lay out the fixtures

Racked areas

  • Run one row of linear high bays down the center of each aisle, not over the racks.
  • Space fixtures along the aisle so the light patterns overlap at the lowest shelf you need to read.
  • Leave room for sprinkler heads, and keep fixtures clear of the path of rack-top loads and forklift masts.
  • If the racking may be moved later, consider a layout or mounting method that can move with it.

Open floor

  • Use a grid of UFO high bays. A common starting point is a spacing roughly equal to the mounting height, adjusted for the target light level.
  • Keep the outer row about half a spacing from the walls so the edges are not dark.
  • Add fixtures over doors, scales, and work benches rather than raising the whole room.

Our lighting layout and spacing guide has spacing rules of thumb for each fixture type. For a job that needs real numbers, send the plan through our free lighting layout request.

Step 6: Add controls

Warehouse aisles can sit empty much of the day. LEDs turn on instantly and do not mind frequent switching, so they pair well with sensors:

  • High-low occupancy sensors dim an aisle to a low level when nobody is there and bring it to full when a person or forklift enters.
  • Daylight sensors dim fixtures near skylights and dock doors on bright days.
  • Time schedules turn the building down after the last shift.

Many energy codes now expect some form of automatic control in warehouses. See 0–10V dimming and lighting controls, photocells and motion sensors, and the motion activated LED lights collection. Always confirm sensor options on each product page.

Step 7: Check power and environment

Worked example: 100 x 200 ft warehouse at 28 ft

  • Building: 20,000 sq ft. Half is pallet racking with 10 aisles, half is open staging.
  • Targets: about 20 fc in the aisles, about 25 fc on the open floor.
  • Racked half: linear high bays in the 150–220W range, one row per aisle, spaced along the aisle so the patterns overlap at the bottom shelf.
  • Open half: 10,000 sq ft × 25 fc ÷ 0.7 (a rough allowance for losses) ≈ 357,000 lumens. With UFOs delivering roughly 30,000 lumens each, that is about 12 fixtures in a 3 x 4 grid, around 25–28 ft apart.
  • Controls: high-low sensors in every aisle, a time schedule for the open floor.

Numbers like these get you close. A photometric layout confirms the real light levels with the actual fixtures.

Replacing old warehouse lighting

Most retrofits replace 400W metal halide or 6-lamp T5HO fixtures. LED high bays typically use a fraction of the power for similar or better light on the floor, and they come on instantly. See the metal halide to LED replacement chart, the fluorescent to LED conversion guide, and LED savings and payback. Utility rebates often apply to listed fixtures; see UL, ETL and DLC listings explained.

Common warehouse lighting mistakes

  • Hanging UFOs over the tops of racks, which wastes light on pallets and leaves the aisles dark.
  • Sizing by wattage instead of by lumens and the target foot-candles.
  • Ignoring the voltage until the fixtures arrive on site.
  • Skipping sensors in aisles that are empty most of the day.
  • Forgetting the dock doors and the truck court outside.

More in our post on warehouse lighting mistakes.

Frequently asked questions

How many foot-candles does a warehouse need?

Typical targets run from about 5–10 fc for bulk storage to 20–30 fc in picking aisles and open floors, and 30–50 fc at packing and shipping benches. Check the needs of the work being done and any local requirements.

How far apart should warehouse high bays be?

For open floors, a spacing close to the mounting height is a common starting point. In racked areas, place one row per aisle and space along the aisle so light overlaps at the lowest shelf.

What color temperature is best for a warehouse?

4000K or 5000K is the usual choice. 5000K reads crisp and bright for labels and scanning. See 3000K vs. 4000K vs. 5000K.

Can you help with a layout?

Yes. Send dimensions, ceiling height, racking layout and voltage through our lighting layout request. Orders ship within 1–3 business days, and our LED fixtures carry a 5-year limited warranty.